Paradox SP5500+ Programming Manual page 59

4 to 32-zone expandable security systems
Table of Contents

Advertisement

SP+ Series Programming Guide
SP5500+ PCB Layout
1 PGM Jumper: allows you to choose whether the solid state
relay PGMs are ground (-), or give out 12V (+)
2 AUX LED:
ON = Aux present; OFF = Aux off
3 Four-pin connector can be used for quick installation of a keypad
4 EBUS and Dialer used with:
VDMP3 Plug-In Voice Module for voice reporting
PCS Series Communicator Module
5
LEDs
Status LED:
Flash once every second: Normal
Flashes ON 1 sec. and OFF 1 sec.: Any trouble
Always ON: Panel is using phone line
Fast flash 6 seconds after power-up: Installer lock enabled
Charge LED:
Charging and battery test LED
6 Panel reset
7 Serial 1: Used as the primary reporting channel for connecting the IP
Module/PCS Module
8 Serial 2: Used as a backup reporting channel for connecting the IP
Module/PCS Module
The sum of the current drawn from the
and lead to complete system shutdown.
40 VA transformer strongly recommended.
This equipment must be installed and maintained by qualified service personnel only.
Max. number of keypads: 15 bus modules
Max. aux. current: 700 mA
Power consumption (idle): 52 mA
Max. distance of bus module from panel: 76 m (250 ft.)
Max. total run of wire: 230 m (750 ft.)
and
must be limited to 1.3A. Exceeding this limit will overload the panel power supply
BELL
AUX
Enter section [300] to
unlock your SP+ panel
serial ports for use with
third-party devices
using a TM70/TM50
Touch keypad and
K32LCD+.
To provide maximum
lightning protection we
strongly recommend having
separate earth connections
for the dialer and zone
ground terminals.
9 Zone Input
10 The
output will shutdown if the current exceeds 3A
BELL
11 PGM output connector
12 AC Power connections
13 Backup Battery connections
14 AWG#14 single conductor solid copper wire
15 Ground clamp
16 Cold water pipe grounding
17 To ground
18 Keypad's zone configuration
19 Zone connections, if EOL is enabled, see section [706] option 2
20 To connect additional wiring to auxiliary power, use the red (+) and black
(-) keypad connectors; auxiliary power will shut down if current exceeds
1.1A; if the auxiliary output is overloaded and shuts down, you must
disconnect all loads from the output for at least 10 sec. before
reconnecting any load back to the auxiliary output
59