Paradox SP5500+ Programming Manual page 41

4 to 32-zone expandable security systems
Table of Contents

Advertisement

SP+ Series Programming Guide
Communication Programming
Use the following section to program various communication features on your SP+ Series control panel. Table 33 lists features available for each
SP+ Series control panel.
Prioritization of signals and messages are based on a "first in, first out" scheme. Systems meet EN 50136 ATS2 or ATS3 requirements when configured as depicted.
NOTE: For increased security, it is suggested that redundant communication methods be installed.
Table 33: Communication features for SP+ Series panels
Communication Feature
GPRS reporting (PCS series)
SMS (PCS series)
IP reporting (IP Module)
E-mail/monitoring (IP Module)
Patented dialer
Dialer Options
Table 34: Description of dialer options for landline communication (section [800])
Option
Description
1 & 2
Telephone line monitoring
3
Switch to pulse on fifth attempt
4
Alternate dial
5
Force dial (must be enabled to comply with TBR-21)
6
DTMF dialing
7
Pulse ratio
8
Reporting*
* This option also applies to landline.
Table 35: Description of general communication dialer options (section [801])
Option
Description
1
Report system disarming
2
Report zone restore
3 & 4
Auto-test report transmission
5
Contact ID override
6
Future Use
7
Future Use
8
Future Use
= Default
Table 36: Auto-test report transmission options (section [801])
Option
3
4
1
OFF
OFF
2
OFF
ON
3
ON
OFF
4
ON
ON
Description
Transmit the test report code when the days programmed in section [840] have elapsed, at the time programmed in section
[850] (default).
When disarmed: transmit test report code when the time programmed in section [852] has elapsed. When armed: transmit test
report code when the time programmed in section [851] has elapsed.
The control panel will transmit the test report code every hour, on the minute value programmed in section [850] (the last two
digits); the first two digits of section [850] will be ignored. For example, if 10:25 was programmed into section [850], the test
report code would be transmitted at the 25th minute of every hour, i.e., 11:25, 12:25, etc.
The test report code will be transmitted when the conditions in entries 2 or 3 above (option 3 = OFF and option 4 = ON; option 3
= ON and option 4 = OFF), are met.
SP5500+
OFF
ON
See options 1
See options 1
& 2, on right
& 2, on right
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
1:2
1:1.5
Dialer
No dialer
activated
OFF
Always
Bell cutoff
See table 36 on page 41
Disabled
-
-
-
-
-
-
Control Panel
SP6000+
SP7000+
Option
Description
1
2
OFF
OFF
Disabled (default)
OFF
ON
Trouble only
When disarmed: trouble only; when
ON
OFF
armed: audible only
ON
ON
Silent alarms become audible alarm
= Default
ON
After alarm
Zone closure
See table 36 on page 41
CID defaults/slow format
custom
-
-
-
-
-
-
41