SP+ Series Programming Guide
Zone Definitions
NOTE: If a device is assigned to a zone which is already programmed, a wireless zone will overwrite a keypad/hardwire zone and a keypad zone will overwrite a
hardwire zone.
To define zones on your SP+ control panel:
1.
Press
, and then enter your installer code (maintenance code may also be used). The
ENTER
2.
Enter the three-digit zone number you wish to program (e.g., 001 to 032). The
3.
Enter a two-digit zone definition, by referring to table 4.
4.
Assign a partition, by referring to table 5. By default, all zones are assigned to partition 1.
5.
Select or deselect zone options, using buttons 1 to 8 (see tables 6 and 7).
6.
Press
to save and proceed to the next zone.
ENTER
7.
Repeat steps 3 to 6 for all remaining zones.
Table 4: Zone definitions for SP+ Series panels
Input Value
00
Disabled (default)
01
02
03
Entry delay 1 (Full Arm)
04
Entry delay 2 (Full Arm)
05
06
Follow (sleep/full arm)
07
Follow (full arm)
08
09
Instant (sleep/full arm)
10
Instant (full arm)
11
12
13
Instant fire silent†
14
Delayed fire silent†
15
16
17
18
19
20
21
22
23
Follow no pre-alarm
24
Instant no pre-alarm
25
Keyswitch maintain**
26
Keyswitch momentary**
33
Instant no pre-alarm (stay/sleep)
34
Instant no pre-alarm (sleep)
35
Entry delay 1 (stay/full)/instant Entry delay 1
36
Entry delay 1 (full arm)/instant
* Flex-instant: zone will follow the delay at section [720] (default is 15 seconds/0 = instant zone).
** On-board, hardwire, control panel zones only.
† ZX8/ZX82 inputs do not support fire zones. For two-wire smoke installations these definitions apply to
zone 1 input only. Section [706], option 3, must be enabled. For four-wire smoke installations, use any panel,
on-board zone input.
‡ This alarm will follow the panic 1 option (section [702], option 1).
Description
Stay Arm
-
Entry delay 1 Entry delay 1
Entry delay 2 Entry delay 2
Not armed
Not armed
Follow
Follow*
Not armed
Not armed
Instant
Instant*
Not armed
Not armed
Instant fire†
-
Delayed fire†
-
-
-
24 hr. buzzer
-
24 hr. burglary
-
24 hr. hold-up
-
24 hr. gas
-
24 hr. heat
-
24 hr. water
-
24 hr. freeze
-
24 hr. panic‡
-
-
-
-
-
Instant
Not armed
Instant
ARM
and
functions will remain illuminated.
ARM
STAY
Arming Type
Sleep Arm
Fully Arm
-
-
Entry delay 1
Entry delay 1
Entry delay 2
Entry delay 2
Not armed
Entry delay 1
Not armed
Entry delay 2
Follow*
Follow
Follow*
Follow
Not armed
Follow
Instant*
Instant
Instant*
Instant
Not armed
Instant
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Instant
Not armed
Instant
Not armed
Instant
Entry delay 1
Instant
Entry delay 1
and
functions will flash.
STAY
Table 5: Partition assignment for SP+ Series panels
Input Value
1
Assign to partition 1
2
Assign to partition 2
3
Assign to both partitions
NOTE: When using the K636 keypad, only
partition 1 is available.
Table 6: Zone options for SP+ Series panels
Input
Description
Value
1
Auto zone shutdown
2
Bypassable zone
3
RF zone supervision
6
Intellizone
7
Delay alarm transmission
8
Force zone
Input Value
4
5
OFF
OFF
OFF
ON
ON
OFF
ON
ON
NOTE: For additional zone options, see Zone
Options on page 37.
Table 7: Keyswitch options for SP+ Series panels
Input
Description
Value
1
2
3
OFF = Disarm; ON = Disarm only
4
if Stay/Sleep armed
5
6
Stay arming*
7
Sleep arming*
8
* Select only one. If all are OFF, keyswitch will
regular arm.
Description
Zone Alarm Type
Audible alarm
Pulsed alarm
Silent alarm
Report only
-
-
-
Arm only
-
13