Idnet Devices Typical Applications - Simplex 4100-S1 Programming Manual

Fire indication panel
Table of Contents

Advertisement

Document: LT0400
6.4

IDNET Devices Typical Applications

The following examples show the programming needed for various ID-Net modules being
used in some common applications.
IAM – Valve Tamper Monitor
1) At the required address add an IAM, Point type SUPERV, Custom Label - Valve Tamper
Monitor. In this example we will use address M1-6-0.
2) If using alternate LED display hardware (4100-1276 8 LEDs only) Tag Device the point into
the required zone List. For example, List L277 for zone 17. Then in point editing of the LED
display add L277 as the reference address. When operated the IAM device will display on
the LCD as an Isolated Valve Tamper.
Relay IAM – AC Trip
1) Program a relay RIAM point type RELAY (M1-8-0 in our example).
2) Add M1-8-0 to track ON into AC Trip Equation under Program 3 in Custom Control Tab
equation 5.
[INPUTS]
STATUS
ON
P521
| DIGITAL | UTILITY | A/C TRIP
AND NOT
STATUS
P517
| DIGITAL | SUPERV | ACF ISOLATE
[END INPUTS]
[OUTPUTS]
TRACK
ON
PRI=9,9
AUX3
| RELAY | RELAY | A/C FIRE TRIP
TRACK
ON
PRI=9,9
M1-8-0
| RIAM | RELAY | AC TRIP
[END OUTPUTS]
TRIAM – Flow Switch / Test Solenoid
1) Program a TRIAM – Point Type UTILITY (M1-7-0 mapping to zone 16 in this example) with
the following sub points.
M1-7-1 – MRELAY – Point Type RELAY – Test Solenoid
M1-7-2 – MTSENSE – Point Type WATER – Flow Switch AZF 16
2) To program the flow switch indication follow the following steps:
3) Tag the sub point 2 (M1-7-2 – MTSENSE – WATER – Flow Switch AZF 16) into List L276, being
the Zone 16 list.
4) Rename L276 to suit the description of the Flow Switch, and remove it from the Fire Brigade
List L256, unless you want the flow switch to call the brigade. Do the same with the AC trip
list L257.
5) Rename P616 (Zone 16 ISO) to be Flow Switch ISO AZF 16.
6) To program the test solenoid follow these steps:
7) With a test solenoid assigned to Zone 16 change P1016 from FIRE to UTILITY because we do
not want it to come up as an ALARM.
8) Create a Custom Control (CC) equation for the output point (M1-7-1 – MRELAY – RELAY –
Test Solenoid) to track the pseudo point as follows.
INPUTS]
STATUS
ON
P1016
| DIGITAL | FIRE | ALARM TEST ZONE 16
[END INPUTS]
[OUTPUTS]
Issue 1.4
SUPV
15 December 2010
4100U-S1 Programming Guide
Addressable Device Settings
AUX3
Page 6-7

Advertisement

Table of Contents
loading

Table of Contents