Adding Zone Displays
7.4

Modify the Custom Control Equations for the Zones

The simplest method to add more custom control equations for the new displays is to open a
32 or 64 zones template and export the custom control equations for the zones, then from
within the original site configuration import these equations. The detailed steps are as follow:
1. Click on the „File‟ menu and select „Open‟.
Browse to the location containing the 3 default configuration templates supplied with
SF0369 and select the S1_64ZN.SDB4100U configuration if more than 32 zones (up to 64)
are needed, or select S1_32ZN.SDB4100U if the configuration should include up to only 32
zones. Click OK.
2. Click on the „Custom
Control‟ tab. Right Click on
Program 4 and select „Export
Program...‟.
Save the exported .CC4100U
file in an accessible location. .
At the end of the export process a message with the
process status will appear with the export result.
Click the OK button.
3.
Close the template and re-open the site configuration database.
Click on the „Custom Control‟ tab.
4.
Right Click on Program 4 and select „Import, Append Program...‟ .
Browse to the location where you saved the exported .CC4100U file, select it and click
„Open'.
The import process will start.
At the end of the import process, a message with the process status will appear with the
import result.
Click the OK button.