4100U-S1 Programming Guide
AS1668 Fan Controls

10.5.2 Set up Register 8

The state of P516 is stored in register 8 and is used in the S/A Detector Isolate and De-
Isolate equations.
[INPUTS]
NOT STATUS ON
P516 | DIGITAL | UTILITY | ALARM OR FAULT TEST ACTIVE
SAVE 8
[END INPUTS]
[OUTPUTS]
[END OUTPUTS]

10.5.3 S/A DETECTOR Isolate

This equation is the same as for zone isolate.
[INPUTS]
STATUS ON
P985 | DIGITAL | UTILITY | MULTIFUNCTION SWITCH - ZONE 85-FAN 1
AND NOT STATUS ON
P685 | DIGITAL | SUPERV | FAN #1
AND NOT STATUS ON
P785 | DIGITAL | UTILITY | ISOLATE TOGGLE ZONE 85 - FAN 1
AND RECALL 8
[END INPUTS]
[OUTPUTS]
HOLD ON PRI=9,9
P685 | DIGITAL | SUPERV | FAN #1
HOLD ON PRI=9,9
P785 | DIGITAL | UTILITY | ISOLATE TOGGLE ZONE 85 - FAN 1
[END OUTPUTS]

10.5.4 S/A DETECTOR De-Isolate

This equation is the same as for zone de-isolate.
[INPUTS]
STATUS ON
P985 | DIGITAL | UTILITY | MULTIFUNCTION SWITCH - ZONE 85-FAN 1
AND STATUS ON
P685 | DIGITAL | SUPERV | FAN #1
AND NOT STATUS ON
P785 | DIGITAL | UTILITY | ISOLATE TOGGLE ZONE 85 - FAN 1
AND RECALL 8
[END INPUTS]
[OUTPUTS]
HOLD OFF PRI=9,9
P685 | DIGITAL | SUPERV | FAN #1 S/A DETECTOR
HOLD ON PRI=9,9
P785 | DIGITAL | UTILITY | ISOLATE TOGGLE ZONE 85 - FAN 1
[END OUTPUTS]
Page 10-10
AZF85
AZF85
AZF85
15 December 2010
Document: LT0400
Issue 1.4