PRESYS
Instruments
DMY-2030-Light-5S-Energy
2.3.3 - Current Input
The 4-20 mA current signal is applied to terminals 5(+) and 6(-). The current
signal can be generated by a transmitter with an external power supply. In case of using
the 24 Vdc internal voltage source from the Indicator to power a two-wire transmitter, the
current is received only by terminal 5(+). Figure 6 shows both possibilities of connection.
Fig. 6 - Current input connections
Installation