PRESYS
 Instruments
Linearization:
 0.1  C for RTD and  0.2  C for TC.
Square root extraction:
 0.5 % of reading, for input above 10% of span. 0 to 5% programmable Cut-off.
Cold junction compensation:
 2.0  C at range from -10 to 60  C ambient temperature.
Thermal stability:
 0.005 % /  C of span with reference of 25  C ambient temperature.
Power Supply:
Universal 75 to 264 Vac 50/60 Hz or 100 to 360 Vdc (any polarity), 10 W nominal;
24 Vac/dc (10 %), 12 Vdc (10 %) and other values are optional.
2-wire transmitter power supply:
24 Vdc voltage and 50 mA maximum, isolated from output, short-circuit protection.
Operating Ambient:
-10 to 60  C temperature and 90% maximum relative humidity.
Dimensions:
1/8 DIN (48 mm x 96 mm x 185 mm), HxWxD,
panel cutout 45 mm x 92 mm, HxW.
Weight:
0.5 kg nominal.
Warranty:
One year.