Presys DMY-2030 Light Technical Manual page 40

Universal digital indicator
Hide thumbs Also See for DMY-2030 Light:
Table of Contents

Advertisement

PRESYS
 Instruments
Voltage input calibration (0 to 500 mV)
To calibrate the voltage input from 0 to 500 mV connect a DC precision voltage
source to terminals 2(+) and 3(-). Are required 6 voltage references listed in the table
below.
Voltage input calibration (1 to 5 V)
To calibrate the voltage input from 1 to 5 V connect a DC precision voltage source
to terminals 2(+) and 3(-). Are required 6 voltage references listed in the table below:
Voltage input calibration (0 to 10 V)
To calibrate the voltage input from 1 to 5 V connect a DC precision voltage source
to terminals 4(+) and 6(-). Are required 6 voltage references listed in the table below:
Current input calibration (4 to 20 mA)
To calibrate the current input from 4 to 20 mA connect a DC precision current
source to terminals 5(+) and 6(-). Are required 6 current references listed in the table
below:
Maintenance
Page 36
Reference
0.000 mV
100.00 mV
200.00 mV
300.00 mV
400.00 mV
500.00 mV
Reference
0.0000 V
1.0000 V
2.0000 V
3.0000 V
4.0000 V
5.0000 V
Reference
0.0000 V
2.0000 V
4.0000 V
6.0000 V
8.0000 V
10.0000 V
DMY-2030-Light-5S-Energy
Mnemonic
C.
0nV
C.100nV
C.200nV
C.300nV
C.400nV
C.500nV
Mnemonic
C. 0V
C. 1V
C. 2V
C. 3V
C. 4V
C. 5V
Mnemonic
C. 0V
C. 2V
C. 4V
C. 6V
C. 8V
C.10V