Common specifications
Surrounding air
temperature
Surrounding air humidity
Storage temperature

Atmosphere
Altitude/vibration

Temperature applicable for a short time, e.g. in transit.

For the installation in an altitude above 1,000 m (up to 2,500 m), derate the rated current 3% per 500 m.

This protective function is not available in the initial status.
94
SPECIFICATIONS
-10°C to +50°C (non-freezing) (LD rating)
-10°C to +40°C (non-freezing) (SLD rating)
With circuit board coating (conforming to IEC60721-3-3 3C2/3S2): 95% RH or less (non-condensing)
Without circuit board coating: 90% RH or less (non-condensing)
-20°C to +65°C
Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt, etc.)
Maximum 1000 m above sea level, 2.9 m/s
2
or less
at 10 to 55 Hz (directions of X, Y, Z axes)
