Peripheral devices
2.1.2
Peripheral devices
Selecting the converter unit (FR-CC2)
Select the capacity of the FR-CC2 converter unit according to the connected motor capacity.
Motor
Converter unit
capacity
FR-CC2-[ ]
(kW)

355
H355K
400
H400K
450
H450K
500
H500K
560
H560K
630
H630K

The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
Selecting the breaker/magnetic contactor
Check the model of the inverter and the converter unit you purchased. Appropriate peripheral devices must be selected
according to the capacity.
Refer to the table below to prepare appropriate peripheral devices.
• 400 V class
Motor
Applicable converter
output
model
(kW)

355
FR-CC2-H355K
400
FR-CC2-H400K
450
FR-CC2-H450K
500
FR-CC2-H500K
560
FR-CC2-H560K
630
FR-CC2-H630K

Assumes the use of a Mitsubishi 4-pole standard motor with the power supply voltage of 400
VAC 50 Hz.

Select an MCCB according to the power supply capacity.
Install one MCCB per converter.
For the use in the United States or Canada, provide the appropriate UL and cUL listed fuse that
is suitable for branch circuit protection. (Refer to

The magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the
magnetic contactor is used for emergency stops during motor driving, the electrical durability is 25 times.
If using an MC for emergency stop during driving the motor, select an MC regarding the converter unit input side current as JEM1038-AC-3 class
rated current. When using an MC on the inverter output side for commercial-power supply operation switching using a general-purpose motor,
select an MC regarding the rated motor current as JEM1038-AC-3 class rated current.
NOTE
• When the converter unit capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to
the converter unit model, and select cables and reactors according to the motor output.
• When the breaker on the converter unit's input side trips, check for the wiring fault (short circuit), damage to internal parts of
the inverter and the converter unit, etc. The cause of the trip must be identified and removed before turning ON the power of
the breaker.
14
INSTALLATION AND WIRING
SLD (superlight duty)
Model
Rated current (A)
FR-F842-[ ]
-
-
-
355K
07700
770
400K
08660
866
450K
09620
962
500K
10940
1094
560K
12120
1212
Molded case circuit breaker (MCCB)
or
earth leakage circuit breaker (ELB)
(NF, NV type)
800A
900A
1000A
1200A
1500A
2000A
page
103.)
Inverter
LD (light duty)
Model
FR-F842-[ ]
355K
07700
400K
08660
450K
09620
500K
10940
560K
12120
-
-

Input-side magnetic contactor
S-N600
S-N800
1000A rated product
1000A rated product
1200A rated product
1400A rated product
MCCB Converter unit
MCCB Converter unit
Rated current (A)
683
770
866
962
1094
-

INV
M
INV
M