Mitsubishi Electric FR-F802 Instruction Manual page 41

Separated converter type
Table of Contents

Advertisement

Control circuit
2.6.4
Wiring of inverter control circuit
Control circuit terminal layout
• Recommended cable gauge: 0.3 to 0.75 mm
2
5
4
1 F/C +24 SD
AM
5 10E 10 SE SE

This terminal operates as the terminal FM for the FM type, and as the terminal CA for the CA type.

The X10 signal is assigned in the initial setting.

No signal is assigned in the initial setting.
Wiring method
• Power supply connection
For the control circuit wiring, strip off the sheath of a cable, and use it with a blade terminal. For a single wire, strip off the
sheath of the wire and apply directly.
Insert the blade terminal or the single wire into a socket of the terminal.
(1) Strip off the sheath for the below length. If the length of the sheath peeled is too long, a short circuit may occur with
neighboring wires. If the length is too short, wires might come off.
Wire the stripped cable after twisting it to prevent it from becoming loose. In addition, do not solder it.
(2) Crimp the blade terminal.
Insert wires to a blade terminal, and check that the wires come out for about 0 to 0.5 mm from a sleeve.
Check the condition of the blade terminal after crimping. Do not use a blade terminal of which the crimping is inappropriate,
or the face is damaged.
• Blade terminals commercially available (as of February 2012)
Phoenix Contact Co., Ltd.
Cable gauge
2
With insulation sleeve
(mm
)
0.3
AI 0, 5-10WH
0.5
AI 0, 5-10WH
0.75
AI 0, 75-10GY
1
AI 1-10RD
1.25, 1.5
AI 1, 5-10BK
AI-TWIN 2  0, 75-10GY
0.75 (for two wires)

A blade terminal with an insulation sleeve compatible with the MTW wire which has a thick wire insulation.

Applicable for the terminals A1, B1, C1, A2, B2, and C2 only.
40
INSTALLATION AND WIRING
2
∗1
So SOC
SD
SIC
S1 S2 PC
RUN
SU
IPF OL FU
PC RL RM RH RT AU
∗3
Cable sheath stripping length
10 mm
Blade terminal model
Without insulation sleeve
-
-
A 0, 75-10
A 1-10
A 1, 5-10
-
A1
B1
C1
A2
B2
STP MRS
RES
SD SD
STF STR JOG
(X10)∗2
Damaged
Crumpled tip
For UL wire
-
AI 0, 5-10WH-GB
AI 0, 75-10GY-GB
AI 1-10RD/1000GB
AI 1, 5-10BK/1000GB
-
C2
CS
∗3
Unstranded
wires
Wires are not inserted
into the sleeve
Crimping tool
name

CRIMPFOX 6


Advertisement

Table of Contents
loading

Table of Contents