Mitsubishi Electric FR-F802 Instruction Manual page 36

Separated converter type
Table of Contents

Advertisement

Terminal
Terminal name
Symbol
RUN
Inverter running
SU
Up to frequency
OL
Overload alarm
IPF
Open collector output
FU
Frequency detection
Open collector output
SE
common
For meter
FM

NPN open
collector output
AM
Analog voltage output
CA
Analog current output


Terminal FM is provided in the FM-type inverter.

Terminal CA is provided in the CA-type inverter.
Communication
Terminal
Terminal name
symbol
PU connector
TXD+
Inverter transmission
terminal
TXD-
RXD+
Inverter reception
terminal
RXD-
SG
Earthing (grounding)
USB A connector
USB B connector
Terminal function description
Switched to LOW when the inverter output frequency is equal to or
higher than the starting frequency (initial value 0.5 Hz). Switched to
HIGH during stop or DC injection brake operation.
Switched to LOW when the output frequency
is within the set frequency range 10% (initial
value). Switched to HIGH during acceleration/
deceleration and at a stop.
Switched to LOW when stall prevention is
activated by the stall prevention function.
Switched to HIGH when stall prevention is
canceled.
No function is assigned in the initial setting.
The function can be assigned setting Pr.192.
Switched to LOW when the inverter output
frequency is equal to or higher than the preset
detection frequency, and to HIGH when it is
less than the preset detection frequency.
Common terminal for terminals RUN, SU, OL, IPF, FU
Outputs a selected monitored item (such as
output frequency) among several monitored
items. The signal is not output during an
inverter reset.
The output signal is proportional to the
magnitude of the corresponding monitoring
item.
Use Pr.55, Pr.56, and Pr.866 to set full scales
for the monitored output frequency, output
current, and torque.
Terminal function description
With the PU connector, communication can be made through RS-485. (For connection on a 1:1
basis only)
Conforming standard: EIA-485 (RS-485)
Transmission format: Multidrop link
Communication speed: 4800 to 115200 bps
Wiring length: 500 m
The RS-485 terminals enable the communication by RS-485.
Conforming standard: EIA-485 (RS-485)
Transmission format: Multidrop link
Communication speed: 300 to 115200 bps
Overall length: 500 m
A connector (receptacle)
A USB memory device enables parameter copies and the
trace function.
Mini B connector (receptacle)
Connected to a personal computer via USB to enable
setting, monitoring, test operations of the inverter by FR
Configurator2.
Control circuit
Rate Specification
Permissible load 24
VDC (maximum 27
VDC) 0.1 A
(The voltage drop is
2.8 V at maximum
while the signal is
ON.)
LOW is when the
Fault code (4 bits)
open collector output
output.
transistor is ON
(conducted).
HIGH is when the
transistor is OFF (not
conducted).
———
Permissible load
Output item:
current 2 mA
Output frequency (initial
For full scale
setting)
1440 pulses/s
This terminal can be
Maximum output
used for open collector
pulse: 50k pulses/s
outputs by setting
Permissible load
Pr.291.
current: 80 mA
Output signal 0 to 10
VDC, Permissible
load current 1 mA
(load impedance 10
Output item:
k or more)
Output frequency (initial
resolution 8 bits
setting)
Load impedance 200
 to 450 
Output signal 0 to 20
mADC
Interface: Conforms to USB1.1
(USB2.0 fullspeed compatible)
Transmission speed: 12 Mbps
INSTALLATION AND WIRING
2
35

Advertisement

Table of Contents
loading

Table of Contents