Safety; O Bus Configuration - ABB ACS880 N5700 Series Firmware Manual

Position control program
Table of Contents

Advertisement

544 Parameters
No.
Name / Range /
Selection
99.19
Sine filter
capacitance
0.00 ... 100000.00 uF
No.
Name / Range /
Selection
200

Safety

No.
Name / Range /
Selection
206
I/O bus
configuration
Description
Defines the capacitance of a custom sine filter, i.e. when
parameter
95.15 Special HW settings
If the capacitors are star/wye-connected, enter the
capacitance of one leg into the parameter.
Drive
Sine filter
If the capacitors are delta-connected, multiply the
capacitance of one leg by 3 and enter the result into
the parameter.
Drive
Sine filter
Note: For an ABB sine filter
bit 1), this parameter is set automatically and should
not be adjusted.
Capacitance of custom sine filter.
Description
FSO-xx settings.
This group contains parameters related to the optional
FSO-xx safety functions module. For details, refer to
the documentation of the FSO-xx module.
Description
Distributed I/O bus settings.
This group is only visible with a BCU control unit.
This group contain parameters related to the
distributed I/O bus, which is used with some drives for
monitoring the cooling fans of the cabinet system. For
details, refer to CIO-01 I/O module for distributed I/O
bus control user's manual (3AXD50000126880
[English]).
bit 3 is activated.
M
3~
C
C
C
99.19 = C
M
3~
C
C
99.19 = 3 × C
C
(95.15 Special HW settings
Def / Type
FbEq 16b / 32b
0.00 uF / real32
100 = 1 uF / 100 = 1
uF
Def / Type
FbEq 16b / 32b
Def / Type
FbEq 16b / 32b

Advertisement