126 Program features

du/dt filter support

With an external du/dt filter connected to the output of the drive, bit 13 of
must be switched on. The setting limits the output switching frequency. With
frame size R5i...R7i inverter modules, the setting also forces the drive/inverter
module fan to full speed. Note that the setting is not to be activated with inverter
modules with internal du/dt filters.

Settings and diagnostics

Parameter:
95.20 HW options word 1 (page

Sine filter support

The control program has a setting that enables the use of sine filters (available
separately from ABB and others).
With an ABB sine filter connected to the output of the drive, bit 1 of
switched on. The setting limits the switching and output frequencies to
prevent the drive from operating at filter resonance frequencies, and
protect the filter from overheating.
With a custom sine filter, bit 3 of
not limit the output frequency.) Additional parameters must be set according to
the properties of the filter as listed below.
Settings and diagnostics
Parameters:
95.15 Special HW settings (page
reference (page
527),
inductance (page 543)
95.15
97.2 Minimum switching frequency (page
and
99.19 Sine filter capacitance (page
513).
must be switched on. (The setting does
511),
97.1 Switching frequency
95.20
95.15
must be
527),
99.18 Sine filter
544).