Omicron DANEO 400 User Manual page 39

Table of Contents

Advertisement

Tip: Instead of dragging the port, double-click the port to map the signal in a quicker way.
By repeating the above procedure for all desired signals, you map the analog and binary signals to the
selected ports of every device.
Remapping signals
To remap signals, which are currently mapped to devices, you must first delete those signals from the
Signal pool. You can only remap a Sampled Value when its voltage and current are both deleted.
This way, the port becomes available again and you can map the signal to a different device.
Creating power systems
To create a valid power system, you must combine a current system and a voltage system. You can
create power systems from mapped and hard-wired phase systems.
To create a power system:
1. From the Analog signals, drag the voltage system to the Power systems. An incomplete
power system appears.
2. From the Analog signals, drag the current system to the incomplete power system created in
step 1.
The power system is now complete and valid.
Tip: Create a power system by dragging a Sampled Value directly onto Power systems.
DANEO Control
39

Advertisement

Table of Contents
loading

Table of Contents