Network; Network Interfaces; Observation; Goose And Sampled Values - Omicron DANEO 400 User Manual

Table of Contents

Advertisement

DANEO 400
Recording: The device is recording.
The Connected clients section shows the list of clients using the device, their IP address, and
whether they are locking the device. The table shows one entry for each client connected to
DANEO Control. Clients connected through the web interface appear only once as "Web interface".
6.2

Network

6.2.1

Network interfaces

The Network section provides similar options as for the Connection options in DANEO Control. For
further details, refer to section "Configuring the connection options" on page 29. In the Network
section of the web interface there is no information about USB connection, but you can find
information about the MAC address of the Ethernet ports.
6.3

Observation

The Observation section provides traffic observation in two forms, packets per second and bytes per
second. Select the Ethernet port to see its traffic statistic in the corresponding diagram.
6.3.1

GOOSE and Sampled Values

The GOOSE and Sampled Values sections provide options for sniffing the network. When you click a
found GOOSE or Sampled Value stream, its Details list appears to the right. The found GOOSE or
Sampled Value stream can be used in Acquisition for configuring the recording filter.
Searching GOOSE and Sampled Values
You can search a GOOSE or Sampled Value stream by entering its destination or source MAC
address or part of it.
You can also search a GOOSE by the control block and dataset reference, and Sampled Values by
their SVID.
6.4

Acquisition

In Acquisition, you can configure and perform recordings. A time trigger condition can be defined to
arm the device for recording and the storage location can be selected.
In the Filters section, you select the ports for recording and configure their traffic filters. A filter can
include GOOSE and SV destination MAC addresses, IPv4 source IP addresses, and other traffic
Ethertypes.
When you select Custom, you can add custom addresses or add the sniffed GOOSE or Sampled
Values from Observation.
The filter options in the web interface slightly differ from the filter options in DANEO Control. The web
interface has the option to select None for GOOSE and SV, which excludes this kind of traffic from the
recording.
Note: An icon appears in the Trigger condition section to indicate that the time in the device is
different of the time in the computer.