Delta Electronics MVF2000 Series Product Manual page 46

Medium voltage drive
Table of Contents

Advertisement

Table 4-23 Input power loss
ID
Parameter
Voltage threshold of
P0484
input power loss
Delay time of input
P1332
power loss detection
Incoming time of
P1333
input voltage
If the voltage values of input three phases are all lower than voltage threshold of input
power loss(P0484), and MCB is still closed after the delay time (P1332) , input power loss
fault is generated.
Table 4-24 Input under voltage
ID
Parameter
Fault action
P1103
configuration: Input
Under Voltage
Fault duration time:
P1253
Input Under Voltage
Threshold of input
P0047
under voltage
While MCB is close, if the RMS value of three phase input voltage is lower than
threshold of input under voltage(P0047) in a duration time of P1253, input under voltage
fault is generated.
Table 4-25 Input over voltage
ID
Parameter
Fault duration time:
P1254
Input Over Voltage
Threshold of input
P0054
over voltage
While MCB is close, if the RMS value of three phase input voltage is higher than
threshold of input over voltage(P0054) in a duration time of P1254, input over voltage
fault is generated.
Table 4-26 Input grounding
ID
Parameter
Fault action
P1105
configuration: Input
Grounding
Fault duration time:
P1255
Input Grounding
Voltage threshold of
P0877
input grounding
If one phase of the input voltage is grounded in a duration time of P1255, input
grounding fault is generated.
Min
Max
100
900
0
65535
0
65535
Min
Max
0
8
0
65535
10
100
Min
Max
0
65535
100
120
Min
Max
0
8
0
65535
100ms
0
100
Unit
Default
Thousanth ratio of
700
rated input voltage
ms
500
s
0
Unit
Default
1
ms
500
Percentage of rated
%
90
input voltage
Unit
Default
ms
0
Percentage of rated
%
110
input voltage
Unit
Default
7
50
%
70
Description
Description
Description
Description