Maintenance Plan - Delta Electronics MVF2000 Series Product Manual

Medium voltage drive
Table of Contents

Advertisement

No tools or foreign objects are left in the cabinets.
All the cabinet doors including protective isolation facilities shall be closed and
ready in position.
5.
Restart the MVD: Operate according to the power-on operation instruction to see
whether there is any abnormity.
6.
Formulate daily record: All the maintenance information (including the revised
parameters) shall be recorded in the daily maintenance record:
Date and time.
Complete maintenance items according to the maintenance plan.
Any special situation or work (planed or unplanned spare parts replacement).

10-2 Maintenance plan

To ensure the long-term steady operation of the equipment, it is necessary for the user to
conduct correct operation and maintenance. The daily protective maintenance and
inspections shall be conducted in a planned way. In addition to the emergency system
maintenance, predictive maintenance shall be conducted, including daily, weekly, monthly,
quarterly and annual inspections and maintenance.
1. Daily maintenance
Maintenance item
Environment
Operating parameter
MVD overall
Cooling fan
Filter
Duration
MVD indoors temperature should in the range of 0~
40℃,25℃ is apporiate
Humidity is lower 95%,no condensation
Air passage type MVD should check the condition of
‐Daily
ventilation
Recommanded record the environment paramenter daily,
check if there is abnormal condition. If abnormal, check the air
condition of air duct.
Check the MVD input voltage is correct or not
Check the MVD operating parameter is normal or not,
and warning / fault record
‐Daily
Check the temperature of trans former is in the normal
range or not(temperateure shown on HMI can't over
90℃).
Check whether MVD is normal, such as oeperating indicator
‐Daily
does not light, abnormal sound, vibration, fire or smell.
Check whether there is abnormal vibration and sound.
‐Daily
Check if there is cooling fan failure and cooling fan power
supply drop alarm.
Check whether the filter is blocked.
Check whther there is air pressure alarm
Recommanded clear the filter at least once 1 week. If the dust
‐Daily
is heavy, the clear duration should be shorten. To disassemble
the filter, please check Maintenance 1.
Recommanded clear method: gently tap it outside the room to
drop off dust. Blow with compressed air slightly. Otherwise
Maintenance detail
111

Advertisement

Table of Contents
loading

Table of Contents