Speed setting analog loss is not detected before running. If the sampling value of the
analog given by the speed is less than the lower threshold or over than the upper
threshold,speed setting analog loss fault is generated
Table 4-41 Encoder abnormal
ID
Parameter
Fault action
P1121
configuration: SVC
Encoder Abnormal
Fault action
P1144
configuration: SLVC
Encoder Abnormal
Fault duration time:
P1271
Encoder Abnormal
Speed error
P0398
threshold for
encoder fault
Loss ratio threshold
P1083
of encoder fault
SVC switch SLVC
P1084
enable for encoder
fault
When the consecutive lost signal of encoder is higher than speed error threshold for
encoder fault(P0398), or the error between encoder speed and estimated speed is
higher than P398, or the encoder signal loss rate per cycle is higher than loss ratio
threshold of encoder fault(P1083), encoder abnormal fault is generated.
Table 4-42 External fault
ID
Parameter
Fault action
P1124
configuration:
External Fault
Fault duration time:
P1274
External Fault
Connect external fault signal wiring to DI of PLC. The switching node should be normal
open. While the switching node is closed, external fault is generated.
Table 4-43 Current sensor power fault
ID
Parameter
Fault action
configuration:
P1125
Current Sensor
Power Fault
Fault duration time:
P1275
Current Sensor
Power Fault
If LEM power board is not energized, current sensor power fault is generated.
Min
Max
Unit
0
8
0
8
0
65535
ms
0
100
0
100
0
1
Min
Max
Unit
0
8
0
65535
ms
Min
Max
Unit
0
8
0
65535
ms
49
Default
2
0
200
%
5
%
10
0-Disable
0
1-Enable
Default
2
0
Default
6
0
Description
Description
Description