Delta Electronics MVF2000 Series Product Manual page 64

Medium voltage drive
Table of Contents

Advertisement

Table 4-56 Torque boost
ID
Parameter
Torque boost
P0004
voltage
Torque boost is used to increase the output voltage during low-frequency operation and
improve the low-frequency torque characteristics of V/F control.
The setting range of the torque boost voltage is 0~300‰. When the set value is 0, there
is no increase, but when the set value is 300‰, the increase range is maximum.
100% rated
Torque boost
voltage(%)
Table 4-57 AVR
ID
Parameter
P0031 AVR enable
Filter bandwidth of
P0953
power cell DC
voltage
AVR function refers to the automatic adjusting function of the output voltage: when the
AVR function is disabled, the output voltage will change with the change of the input
voltage (or the DC bus voltage); when the AVR function is enabled, the output voltage
will not change with the change of the input voltage (or the DC bus voltage), and the
output voltage will basically keep constant within the normal input voltage variation
range.
Table 4-58 Dead-band compensation
ID
Parameter
Dead-band
P0960
compensation
enable
Min
0
voltage
Fig. 4-5 Torque boost
Min
0
0
Min
0
Max
Unit
Default
300
Rated
frequency
Max
Unit
Default
1
65535
0.01Hz
Max
Unit
Default
1
Description
0
Description
0-Disable
0
1-Enable
20
Description
0-Disable
0
1-Enable