Locating Your Gas Appliance; Manufactured Mobile Home Additional Requirements; Heatwave Duct System Optional Kit; Clearances - Regency Fireplace Products Excalibur P90EX Owners & Installation Manual

Zero clearance direct vent gas fireplace
Table of Contents

Advertisement

Locating Your
Gas fireplace
1. When selecting a location for your fireplace,
ensure that the clearances outlined on this
page are met.
2. Provide adequate clearances for servicing.
3. The appliance must be installed on a flat, solid,
continuous surface (e.g. wood, metal, concrete).
This may be the floor, or raised up on a platform
to enhance its visual impact. If the appliance is
going to be installed on carpeting, combustible
linoleum tile or other combustible material other
than wood flooring, the appliance must be
installed on a metal or wood panel extending
the full width and depth of the appliance.
4. The P90EX Direct Vent Gas Fireplace
can be installed in a recessed position or
framed out into the room as in A, B, C, D.
See Diagram 1.
A) Flat on Wall
B) Flat on Wall Corner
C) Recessed into
Wall/Alcove
D) Corner
Diagram 1
5. This appliance is Listed for bedroom installations
when used with a Listed Millivolt Thermostat.
Some areas may have further requirements,
check local codes before installation.
6. The P90EX Direct Vent Gas Fireplace is
approved for alcove installations, which meet
the clearances listed on this page.
7. We recommend that you plan your installa-
tion on paper using exact measurements for
clearances and floor protection before actu-
ally installing this appliance. Have a qualified
inspector, dealer, or installer review your plans
before installation.
Note:
For vent terminations see the
"Exterior Vent Termination
Locations" section.
Manufactured Mobile Home
Additional Requirements
1. Ensure that structural members are not cut or
weakened during installation.
2. Ensure proper grounding using the #8 ground
lug provided. See the "Wiring Diagram" section.
HeatWave Duct System
Optional Kit #946-556
The HeatWave Air Duct Kit increases the
effectiveness of your fireplace by dispersing warm
air from the fireplace to remote locations in the
same room or other rooms in your home.
Up to two kits may be installed on the fireplace.
Please Note: Only 1 HeatWave kit may be operated
at one time. This includes the internal blower
option as well.

Clearances

The clearances listed are Minimum distances unless
otherwise stated:
A major cause of chimney related fires is
failure to maintain required clearances (air
space) to combustible materials. It is of the
greatest importance that this fireplace and
vent system be installed only in accordance
with these instructions.
Clearance to Combustibles from:
Back
Side
Floor
(below firebox base)
NOTE: The minimum floor clearance must
be maintained from the top surface of
the carpeting, tile, etc.
See Hearth Requirements in this manual.
Side Wall Clearance
Horizontal Vent Clearances
Top
Side
Bottom
Vertical Vent Clearances 1-1/4" (32mm)
Alcove Clearances**:
Max. Depth
Min. Width
Min. Height
* See mantle clearance instructions
(Refer to the "Combustible Mantels" section).
WARNING:
Fire hazard is an extreme risk if
these clearances are not adhered
to.
Clearances for HeatWave Kit
The HeatWave Duct Kit has different
clearance and framing requirements, check
the HeatWave manual for details.
Regency Excalibur
P90EX Direct Vent Gas Stove |
®
installation
0"
(0mm)
0"
(0mm)
0"
(0mm)
6-1/2" (165mm)
2-1/2" (64mm)
1-1/2" (38mm)
1-1/2" (38mm)
36"
(914mm)
72"
(1829mm)
72"
(1829mm)
17