Perfect Harmony GENIII/e User's Manual
Parameter
Input Protection
Drive IOC Setpoint
Cell Overload Level
Auto Reset Enable
Auto Reset Time
Auto Reset Attempts
Auto Reset Memory Time
Fault Reset
A1A19000405A: Version 1.3
Table 3-55: Drive Protect Menu (7) Parameters
ID
Units
Default
7000
Submenu
7110
%
150.0
7112
%
100.0
7120
No
7130
sec
1
7140
4
7150
sec
10
7160
Function
s s s s
The Keypad and Display Interface
Min
Max
Description
Input protection parameters. See
Table 3-56.
Drive instantaneous overcurrent
50.0
200.0
setpoint (as a percentage of drive
output rating).
Cell current overload (as a
percentage of drive output
100.0
150.0
rating) allowed for 1 minute out
of every 10 minutes.
Enables the reset of the Drive
after a fault.
Adjusts the time between the
0
120
fault and its automatic reset.
The number of attempts a drive
1
10
will be reset before a permanent
shutdown.
The amount of time between
1
1000
faults that will clear the attempts
counter.
Issues a Drive fault reset when
selected.
3
3-59