Table 2-6: 6,600 VAC GENIII Cell Specifications: 18 Cells Total, 6 (630 VAC) Cells in Series
1
2
Hp
Amps In
Amps Out
600
48
70
700
56
70
800
64
70
900
72
100
1000
80
100
1250
100
100
1500
120
140
1750
140
140
1750
141
200
2000
162
200
2250
182
200
2500
202
260
2750
222
260
3000
242
260
Table 2-7: 2,300 VAC GENIII/e Cell Specifications: 6 Cells Total, 2 (690 VAC) Cells in Series
1
2
Hp
Amps In
Amps Out
1500
324
375
1750
378
375
2000
432
500
2250
486
500
2500
540
660
3000
648
660
Table 2-8: 3,300 VAC GENIII/e Cell Specifications: 9 Cells Total, 3 (690 VAC) Cells in Series
1
2
Hp
Amps In
Amps Out
1750
264
315
2000
301
315
2250
339
375
A1A19000405A: Version 1.3
3
4
Losses
Ventilation
60,000
8,800
70,000
8,800
80,000
8,800
90,000
8,800
100,000
8,800
125,000
8,800
150,000
8,800
175,000
8,800
175,000
13,200
200,000
13,200
225,000
13,200
250,000
13,200
275,000
13,200
300,000
13,200
3
4
Losses
Ventilation
114,000
8,800
133,000
8,800
152,000
8,800
171,000
8,800
190,000
8,800
228,000
8,800
3
4
Losses
Ventilation
133,000
15,000
152,000
15,000
171,000
15,000
s s s s
Hardware Components
5
6
Length
Weight
137
7,700
137
9,000
137
9,000
137
9,000
137
10,400
137
10,400
137
12,300
137
12,300
192
12,500
192
13,000
192
13,000
192
13,500
192
14,000
192
14,000
5
6
Length
Weight
172
7,450
172
8,200
172
8,800
172
9,500
172
10,200
172
11,500
5
6
Length
Weight
172
9,700
172
11,200
172
11,200
7
8
Size
2
70
70
70
100
100
100
140
140
200
200
200
260
260
260
7
8
Size
375H
375H
500H
500H
660H
660H
7
8
Size
315H
315H
375H
2-13