Siemens PERFECT HARMONY GENIII/E Series User Manual page 59

Air cooled
Table of Contents

Advertisement

Perfect Harmony GENIII/e User's Manual
Parameter
ID
Motor frequency
1020
Full load speed
1030
Motor voltage
1040
Full load current
1050
No load current
1060
Motor kW rating
1010
Leakage inductance
1070
Stator resistance
1080
Inertia
1090
A1A19000405A: Version 1.3
Table 3-7: Motor Parameter Menu (1000)
Units
Default
Min
Hz
60
15
RPM
1780
1
V
4160
380
A
125.0
12.0
%
25.0
0.0
kW
746.0
120.0
%
16.0
0.0
%
0.10
0.00
2
30.0
0.0
Kgm
s s s s
The Keypad and Display Interface
Max
Description
Enter the rated or base frequency of
330
the motor from the nameplate.
Enter the full load speed of the motor
19800
from the nameplate.
Enter the rated voltage for the motor
13800
from the nameplate.
Enter the rated nameplate full load
1500.0
current of the motor.
Enter the no load current of the motor
100.0
if it is provided, or use the Auto-tune
function.
Enter the motor kW (0.746 * Hp)
20000.0
from the nameplate.
Enter the leakage inductance of the
30.0
motor if it is provided, or use the
Auto-tune function.
Enter the stator resistance of the
motor if it is provided. To convert
from ohms to %, use the formula:
25.00
[%Rs = 100 * √3 * Rs (in ohms) *
Motor Current/Motor Voltage], or use
the Auto-Tune function.
Enter the rotor inertia of the motor if
100000.0
known (1Kgm
the Auto-Tune function.
2
2
= 23.24 lbft
), or use
3-23