Siemens PERFECT HARMONY GENIII/E Series User Manual page 29

Air cooled
Table of Contents

Advertisement

Perfect Harmony GENIII/e User's Manual
Table 2-11: 6,600 VAC GENIII/e Cell Specifications: 18 Cells Total, 6 (690 VAC) Cells in Series
1
2
Hp
Amps In
Amps Out
3500
264
315
4000
301
315
5000
377
375
6000
452
500
7000
527
660
8000
603
660
1. Motor nameplate Hp may not exceed the drive rated Hp.
2. Drive rated input current (in Amps) is the transformer rated current.
3. Drive rated output current (in Amps) is the maximum cell current.
4. Losses are given in BTU/hr and are based on a loss of 3 kW per 100 Hp.
5. Minimum ventilation requirements are given in CFM (lps in parentheses).
6. Represents lineup minimum length in inches (centimeters in parentheses), subject to change.
7. Represents estimated minimum weight of lineup in pounds (kg in parentheses), subject to change.
8. Cell sizes for each Hp are based on motors with ≥ 95% efficiency and ≥ 85% power factor.
The basic electrical diagrams for all Perfect Harmony systems are similar. Depending on the operating voltages,
different numbers of output cells are operated in series to develop the required output operating voltage (refer to the
previous tables).
A1A19000405A: Version 1.3
3
4
Losses
Ventilation
266,000
28,000
304,000
28,000
380,000
28,000
450,000
28,000
532,000
28,000
608,000
28,000
s s s s
Hardware Components
5
6
Length
Weight
248
21,900
272
23,800
272
27,700
272
31,600
272
35,500
272
39,400
7
8
Size
2
315H
315H
375H
500H
660H
660H
2-15

Advertisement

Table of Contents
loading

Table of Contents