Parameter
ID
Phase I gain
2710
Phase P gain
2720
Phase offset
2730
deg
Phase error
2740
deg
threshold
Frequency
2750
%
Offset
Up Transfer
2760
sec
Timeout
Down
Transfer
2770
Sec
Timeout
Parameter
ID
Analog Inputs
2810
Analog Outputs
2820
Digital Inputs
2830
Digital Outputs
2840
2850
Wago
timeout
A1A19000405A: Version 1.3
Table 3-19: Sync Transfer Menu (2700)
Units
Default
Min
2.0
0.0
4.0
1.0
2.0
-90.0
1.5
0.0
0.5
-10.0
0.0
0.0
0.0
0.0
Table 3-20: External I/O Menu (2800)
Units
Default
Min
0
0
0
0
0
0
0
0
sec
0
0
s s s s
The Keypad and Display Interface
Max
Description
Integral gain of the phase loop used dur-
15.0
ing Up transfer.
Proportional gain of the phase loop used
12.0
during Up Transfer.
Phase offset provided at the input of the
90.0
phase loop to adjust phase errors due to
sampling. The typical value is 2 degrees.
Phase error level that is used to determine
5.0
if phase lock has been achieved during
Up Transfer.
Frequency offset provided at the input of
10.0
the speed loop to force the drive to
Torque limit drive Down Transfer.
If the time taken for Up Transfer exceeds
600.0
this value then an Up Transfer Timeout
Fault is generated.
If the time taken for Down Transfer
600.0
exceeds this value then a Down Transfer
Timeout Fault is generated.
Max
Description
Sets the quantity of analog inputs in the
24
attached external I/O.
Sets the quantity of analog outputs in the
16
attached external I/O.
Sets the quantity of digital inputs in the
96
attached external I/O.
Sets the quantity of digital outputs in the
64
attached external I/O.
600
Sets the Wago
watchdog timeout period.
3
3-35