Perfect Harmony GENIII/e User's Manual
Parameter
ID
Underload enable
1180
I underload
1182
Underload timeout
1186
Motor torque limit 1
1190
Regen torque limit 1
1200
Motor torque limit 2
1210
Regen torque limit 2
1220
Motor torque limit 3
1230
Regen torque limit 3
1240
Phase Imbalance
1244
Limit
Ground Fault Limit
1245
Ground Fault Time
1246
Const
A1A19000405A: Version 1.3
Units
Default
Min
Disable
%
10.0
1.0
sec
10.0
0.01
%
100.0
0.0
%
-0.3
-300.0
%
100.0
0.0
%
-0.3
-300.0
%
100.0
0.0
%
-0.3
-300.0
%
40.0
0.0
%
5.0
0.0
sec
0.017
0.001
s s s s
The Keypad and Display Interface
Max
Description
Enables or disables underload
protection.
Sets the current underload level based
90.0
on the rated motor current.
900.0
Sets the time for underload trip.
Sets the motoring torque limit as a
300.0
function of the rated motor current.
Sets the regenerative torque limit as a
function of rated motor current at full
0.0
speed. The limit is allowed to increase
inversely with speed.
Sets the motoring torque limit as a
300.0
function of the available motor
current.
Sets the regenerative torque limit as a
function of rated motor current at full
0.0
speed. The limit is allowed to increase
inversely with speed.
Sets the motoring torque limit as a
300.0
function of the available motor
current.
Sets the regenerative torque limit as a
function of rated motor current at full
0.0
speed. The limit is allowed to increase
inversely with speed.
Sets the current threshold level for the
100.0
output phase current imbalance alarm.
Sets the threshold of voltage for the
100.0
output ground fault alarm.
Sets the filter time constant for
averaging the ground voltage and
2.000
delaying the response of the ground
fault detection.
3
3-25