The Keypad and Display Interface
Parameter
Accel time 1
Decel time 1
3
Accel time 2
Decel time 2
Accel time 3
Decel time 3
Jerk rate
Parameter
Skip center freq 1
Skip center freq 2
Skip center freq 3
Skip bandwidth 1
Skip bandwidth 2
Skip bandwidth 3
Freq avoid accel time
The critical frequency feature (sometimes called resonance avoidance) is accomplished using skip frequencies and
skip bands as defined in Table 3-16. This is illustrated in Figure 3-22.
3-30
Table 3-14: Speed Ramp Setup Menu (2260)
ID
Units
Default
2270
sec
5.0
2280
sec
5.0
2290
sec
5.0
2300
sec
5.0
2310
sec
50.0
2320
sec
50.0
2330
0.1
Table 3-15: Critical Frequency Menu (2340)
ID
Units
2350
Hz
15.0
2360
Hz
30.0
2370
Hz
45.0
2380
Hz
0.0
2390
Hz
0.0
2400
Hz
0.0
2410
sec
5.0
s s s s
Perfect Harmony GENIII/e User's Manual
Min
Max
0.0
3200.0
Acceleration time 1 in seconds.
0.0
3200.0
Deceleration time 1 in seconds.
0.0
3200.0
Acceleration time 2 in seconds.
0.0
3200.0
Deceleration time 2 in seconds.
0.0
3200.0
Acceleration time 3 in seconds.
0.0
3200.0
Deceleration time 3 in seconds.
Jerk rate in time to reach an
0.0
3200.0
acceleration rate that will achieve rated
velocity in 1 sec.
Default
Min
Max
0.0
360.0
0.0
360.0
0.0
360.0
0.0
6.0
0.0
6.0
0.0
6.0
0.0
180.0
Description
Description
Enter the center of the first critical
frequency band to be avoided.
Enter the center of the second
critical frequency band to be
avoided.
Enter the center of the third critical
frequency band to be avoided.
Enter the bandwidth of the first
critical frequency band to be
avoided.
Enter the bandwidth of the second
critical frequency band to be
avoided.
Enter the bandwidth of the third
critical frequency band to be
avoided.
The accelerate used to pass through