Programming And Use Of The Zone Remote Panel; Rs-485 Modbus Converter Configuration - Immergas TRIO PACK HYBRID 4 Instructions And Warnings

Heat pump consisting of: indoor unit ui tph - victrix tera 24 plus, condensing boiler, outdoor condensing unit audax pro 4 - 6 - 9 v2
Table of Contents

Advertisement

3.9
PROGRAMMING AND USE
OF THE ZONE REMOTE PANEL.
Trio Pack Hybrid remote panel on zone 1 and Remote zone
panel on zone 2.
Trio Pack Hybrid remote panel
Assistance Menu -> System definition -> Main zone: .............................................1
Assistance Menu -> Zone 1 Definition ->
Remote control enabling: ...................................................................................... NO
Assistance Menu -> Zone 2 Definition ->
Remote control enabling: ................................................................................... Panel
Trio Pack Hybrid remote panel on zone 2 and Remote zone
panel on zone 1.
Remote zone control
Assistance Menu -> Device configuration -> Slave address: 41
Assistance Menu -> Device configuration -> Baud rate: 9600
Assistance Menu -> Device configuration -> Parity bit: Even
Assistance Menu -> Device configuration -> Stop Bits: 1
Assistance Menu -> Device configuration -> Heat pump control: NO
3.10 RS-485 MODBUS CONVERTER
CONFIGURATION.
To ensure communication between the supervision board and the
boiler, check the correct configuration of the DIP-SWITCHES of
the RS-485 Modbus module (Ref. Fig. 54).
ON
1
Zone 1
Zone 1
2
3
4
5
Assistance Menu -> Device configuration -> Slave address: 42
Assistance Menu -> Device configuration -> Baud rate: 9600
Assistance Menu -> Device configuration -> Parity bit: Even
Assistance Menu -> Device configuration -> Stop Bits: 1
Assistance Menu -> Device configuration -> Heat pump control: NO
Assistance Menu -> System definition -> Main zone: .............................................2
Assistance Menu -> Zone 1 Definition ->
Remote control enabling: ................................................................................... Panel
Assistance Menu -> Zone 2 Definition ->
Remote control enabling: ...................................................................................... NO
54
Zone 2
Remote zone control
Zone 2
Trio Pack Hybrid remote panel
71

Advertisement

Table of Contents
loading

Table of Contents