Conjunction Mode; Heat Pump Disabling Function; Diverter Valve Management (Summer / Winter) (Optional); External Probe Setting (Optional) - Immergas TRIO PACK HYBRID 4 Instructions And Warnings

Heat pump consisting of: indoor unit ui tph - victrix tera 24 plus, condensing boiler, outdoor condensing unit audax pro 4 - 6 - 9 v2
Table of Contents

Advertisement

3.20 CONJUNCTION MODE.

In case of simultaneous DHW (Domestic hot water) and system
request, the system decides which to service to perform on the
basis of an alternating logic determined by the system.
It is possible to modify this logic, so that the system simultaneously
deals with both services, using the generators available.
IT IS possible to activate operation in this mode by modifying
the parameter:
Integration/Conjunction mode.

3.21 HEAT PUMP DISABLING FUNCTION.

With a closed contact (contact "S43" Fig. 20) the heat pump op-
eration is inhibited. No request will be met, excluding the safety
functions.
To enable this function, it is necessary to modify the parameter:
System definition/Contact Disab. HP = Yes
3.22 DIVERTER VALVE MANAGEMENT
(SUMMER / WINTER) (OPTIONAL).
Valid only in conjunction with relay kit 2.
The unit electronics has a 230V outlet to manage the
summer / winter diverter valves.
The voltage output is active when the appliance is in SUMMER
mode with Cooling.
3.23 EXTERNAL PROBE SETTING
(OPTIONAL).
To activate the optional external probe, it is necessary to modify
the parameter:
System definition/Temperature control/External probe.
If the temperature probe is particular far from the indoor unit, it
is possible to correct its value by modifying:
System definition/Temperature control/External probe correct.

3.24 MANUAL DRIVES

In the menu:
Assistance/Manual
it is possible to manage all the main appliance loads in manual
mode.
These parameters must be used in case of system troubleshooting.
To correctly activate the functions, it is necessary to set the system
in "stand-by".
74
3.25 OUTDOOR CONDENSING UNIT TEST
MODE FUNCTION.
When test mode is used (see Outdoor condensing unit instruc-
tion booklet), the indoor unit must be set in a mode other than
"Stand-by".
The alarm 183 is triggered during the test, meaning "Test mode"
in progress.
3.26 OUTDOOR CONDENSING UNIT PUMP
DOWN FUNCTION.
If the pump down function is used (see outdoor condensing unit
instruction booklet) the indoor unit must be set in "Stand-by".
The function can only be activated if the appliance is not under
alarm.
3.27 SUPERVISION DEVICE
CONFIGURATION.
The appliance can be configured so that it can be controlled by
the external supervision devices such as Dominus or other types
of home automation systems (not supplied by Immergas).
For the configuration, it is necessary to modify the parameter:
System definition/System supervision.
It is not possible to configure both devices simulta-
neously.