The Module Properties dialog box has tabs if you checked Open Module
Properties on the New Module dialog box.
The Connection tab defaults as shown in the example.
8. Click OK.

Add the Logix Blocks

The Logix Block facilitates cascading control between a ControlLogix
environment and a fieldbus environment. The Logic Block takes signals
generated in either environment and sends them to the other.
You can use the Logix Block to send or receive 8 analog or 8 discrete signals per
Logix Block to or from a Logix controller. You can use up to 16 Logix Block
within a single linking device.
See
Logix Block Module Operation
how the Logix Block module operates in a ControlLogix system.
Do these steps to add a Logix Block module to the linking device.
1. In the Controller organizer, right-click the 1757-FFLD module and
choose New Module.