Introduction

1757-FFLD
Status Indicators
Troubleshoot the Linking Device
This appendix describes options for troubleshooting the 1757-FFLDx and the
1757-FFLDCx linking devices.
The table describes the topics in this section.
Topic

1757-FFLD Status Indicators

1757-FFLDC Status Indicators
ControlNet Network Status Indicators
Reset the Linking Device
The table provides a description of the status indicators to evaluate the
performance of the 1757-FFLD linking device.
Table 12 - 1757-FFLD Status Indicators
Indicator
H1
STATUS
(module)
WDOG
(\watchdog)
BATT
(battery)
Rockwell Automation Publication 1757-UM012A-EN-P - July 2011
Status
Description
Off
The H1 channel is inactive.
Verify that the linking device is connected to the
H1 network.
Flashing green
The linking device H1 channel is active.
Off
No power - Module does not have 24V DC power.
Flashing green
Standby - Module is not configured or a duplicate IP
address is detected.
Configure the module. Assign a new IP address.
Solid green
Operational - Module is operating correctly.
Flashing red
Minor fault - A recoverable fault has been detected.
Verify that the configuration is correct and
consistent.
Solid red
Major fault - An unrecoverable fault has been
detected.
Recycle power to the module. If this does not clear
the fault, replace the module.
Off
Normal operation.
Flashing red
Software fault.
Contact Rockwell Automation Technical Support at
http://www.rockwellautomation.com/support/.
Off
Normal operation.
Flashing red
Jumper is missing (or not seated on the two
rightmost pins), or the battery is low or dead
A
Appendix
Page
145
146
147
149
(1)
145