Appendix F
HSE Network Setup Tool

Activate 1757-FFLD

Linking Devices

170
3. Click the Save icon
The HSE OPC Server uses the selected network card to connect to the
HSE Network.
This configuration selection affects only the HSE OPC Server. No Windows
system configuration is affected.
An active 1757-FFLD linking device can be used by any client connected to the
HSE OPC Server; while an inactive linking device cannot be used. An active
linking device is seen on the RSFieldbus Live List and can be used in RSFieldbus
software projects.
By default, linking devices with the same subnet mask as the active network card
are active. Linking devices with a different subnet mask than the active network
card are inactive.
Linking devices with a different subnet mask than the active network card can be
activated for use by clients connected to the HSE OPC Server, regardless of the
subnet mask.
Do these steps to activate a 1757-FFLD linking device.
1. On the HSE Network Setup Tool dialog box, check the corresponding
checkbox in the Device Active column.
2. Click the Save icon
The linking device is active and can be seen on the RSFieldbus Live List.
Rockwell Automation Publication 1757-UM012A-EN-P - July 2011
.
.