Chapter 7
Linking Device Function Blocks
Table 5 - RES Block Parameters
Index Parameter
Data Type
(length)
29
SET_FSTATE
Unsigned8
30
CLR_FSTATE
Unsigned8
31
MAX_NOTIFY
Unsigned8
32
LIM_NOTIFY
Unsigned8
33
CONFIRM_TIME Unsigned32
34
WRITE_LOCK
Unsigned8
35
UPDATE_EVT
DS-73
36
BLOCK_ALM
DS-72
37
ALARM_SUM
DS-74
38
ACK_OPTION
Bitstring(2)
39
WRITE_PRI
Unsigned8
40
WRITE_ALM
DS-72
41
ITK_VER
Unsigned16
110
Valid Range/
Default
Options
Value
1: Off
1
2: Set
1: Off
1
2: Clear
Set by mfgr
3
0 to MAX_
MAX_
NOTIFY
NOTIFY
640000
1:Not Locked
1
2:Locked
See
ALARM_SUM
and
ACK_OPTION
Bits on page 110
0: Auto ACK
0
Disable
1: Auto ACK
Enable
0 to 15
0

Resource Function Block Options

Table 6
describes the options with the resource block.
Table 6 - Block Options
Bit
Meaning
ALARM_SUM and ACK_OPTION Bits
0
Writes have been enabled
1–6
Reserved
7
Block alarm
Rockwell Automation Publication 1757-UM012A-EN-P - July 2011
Units
Edit
Description
Mode
E
AUTO
Allows the fault state condition to be manually
initiated by selecting Set.
E
AUTO
Writing a Clear to this parameter will clear the device
fault state if the field condition, if any, has cleared.
None
RO
Not user configurable.
None
RO
Not user configurable.
1/32 ms
AUTO
Not user configurable.
E
AUTO
If set, no writes from anywhere are allowed, except to
clear WRITE_LOCK. Block inputs will continue to be
updated.
N/A
RO
This alert is generated by any change to the static data.
N/A
RO
The block alarm is used for all configuration, hardware,
connection failure or system anomalies in the block.
The cause of the alert is entered in the subcode field.
The first alert to become active will set the Active
status in the Status attribute. As soon as the
Unreported status is cleared by the alert reporting task,
another block alert may be reported without clearing
the Active status, if the subcode has changed.
N/A
RO
The current alert status, unacknowledged states,
unreported states, and disabled states of the alarms
associated with the function block.
N/A
AUTO
Selection of whether alarms associated with the block
will be automatically acknowledged. See
ALARM_SUM and ACK_OPTION on
None
AUTO
Priority of the alarm generated by clearing the write
lock.
None
RO
This alert is generated if the write lock parameter is
cleared.
N/A
RO
This parameter specifies to which ITK version the
device is certified (only for certified devices).
page
110.