Reset Through Rsfieldbus Software - Allen-Bradley 9308-RSFB64ENE User Manual

Table of Contents

Advertisement

2. Press the reset button.
Reset Configuration Jumper

Reset through RSFieldbus Software

By using RSFieldbus software, you can reset the linking device through the
Restart parameter in the Resource block.
ATTENTION: You will lose the following linking device functions during
a reset:
Control of the current linking device process
Monitoring processes through the linking device
Communication to devices attached to the linking device
1. While online in RSFieldbus software, right-click the Resource block of the
linking device and choose Online Characterization.
2. Select the Restart parameter and click Edit.
3. On the pull-down menu, choose the type of reset identified in the table.
Value
1
2
3
4
5
Rockwell Automation Publication 1757-UM012A-EN-P - July 2011
Troubleshoot the Linking Device
Reset Type
Description
Run
Run appears while the linking device is operating
normally. It returns to this value after a reset value
(default or factory) is transmitted
and completed.
Resource
Not supported (do not select).
Defaults
This resets all block parameters to default. All
blocks in the linking device are retained, including
tag names, and macrocycle times.
Processor
Not supported (do not select).
Factory
This deletes all blocks in the linking device except
for the Resource block. All Resource block
parameters are reset to factory default, including
the tag name.
Appendix A
Factory-default Reset Button
(inside top cover)
43481-C