Linking Device Function Blocks
Table 5 - RES Block Parameters
Index Parameter
Data Type
(length)
1
ST_REV
Unsigned16
2
TAG_DESC
OctString(32)
3
STRATEGY
Unsigned16
4
ALERT_KEY
Unsigned8
5
MODE_BLK
DS-69
6

BLOCK_ERR

Bitstring(2)
7
RS_STATE
Unsigned8
8
TEST_RW
DS-85
9
DD_RESOURCE
Visible String(32)
108

Supported Modes

Out of Service (OOS) and AUTO are supported modes for the linking device.
BLOCK_ERR
The BLOCK_ERR of the resource block indicates the following causes for the
error:
• Device Fault State Set – When FAULT_STATE is active.
• Out of Service – When the block is in OOS mode.
Block Configuration Out of Service - Incorrect parameter value or uninitialized
value for a parameter that requires a value or selection for the block to operate.

Parameters

Table 5
describes the resource block parameters.
See
page 155
for Data Type and Structure definitions
Valid Range/
Default
Options
Value
2 bytes
0
4 bytes
Spaces
2 bytes
0
1 byte,
0
1 to 255
OOS
Spaces
Rockwell Automation Publication 1757-UM012A-EN-P - July 2011
Units
Edit
Description
Mode
None
RO
The revision level of the static data associated with the
function block. The revision value will be incremented
each time a static parameter value in the block is
changed.
N/A
AUTO
The user description of the intended application of the
block.
None
AUTO
The strategy field can be used to identify grouping of
blocks. This data is not checked or processed by the
block.
None
AUTO
The identification number of the plant unit. This
information may be used in the host for sorting alarms,
and so on.
N/A
AUTO
See MODE Block Parameter in Chapter 2 of the
FOUNDATION Fieldbus Design Considerations
Reference Manual, publication RSFBUS-RM001.
E
RO
This parameter reflects the error status associated
with the hardware or software components associated
with a block. It is a bit string, so that multiple errors
may be shown.
E
RO
State of the function block application state machine.
None
AUTO
Read/write test parameter - used only for conformance
testing.
N/A
RO
Not user configurable.
.