Parameters - Allen-Bradley 9308-RSFB64ENE User Manual

Table of Contents

Advertisement

Chapter 7
Linking Device Function Blocks
Table 8 - LGX Block Parameters
Index Parameter
Data Type
(length)
1
ST_REV
Unsigned16
2
TAG_DESC
OctString(32)
3
STRATEGY
Unsigned16
4
ALERT_KEY
Unsigned8
5
MODE_BLK
DS-69
6
BLOCK_ERR
Bitstring(2)
7
SLOT
8–15
IN_0– IN_7
DS-66
16–23 IN_D0–IN_D7
DS-65
24–31 OUT_0–OUT_7
DS-65
32–39 OUT_D0–OUT_D7
DS-65
40
UPDATE_EVT
DS-73
41
BLOCK_ALM
DS-72
116

Parameters

Table 8
describes parameters for the Logix Block.
See
page 155
for data type and structure definitions
Valid Range/
Default
Options
Value
0
Spaces
0
1 to 255
0
OOS
0 to 15
0
Rockwell Automation Publication 1757-UM012A-EN-P - July 2011
Units
Edit
Description
Mode
None
RO
The revision level of the static data associated with the
function block. The revision value is incremented each
time a static parameter value in the block is changed.
N/A
AUTO
The user description of the intended application of the
block.
None
AUTO
Can be used to identify grouping of blocks. This data is
not checked or processed by the block.
None
AUTO
The identification number of the plant unit.
N/A
AUTO
See MODE Block Parameter in Chater 2 of the
FOUNDATION Fieldbus Design Considerations
Reference Manual, publication RSFBUS-RM001.
E
RO
Reflects the error status associated with the hardware
or software components associated with a block.
Because it is a bitstring, multiple errors can be shown.
OOS
Identifies the virtual slot location of the Logix Block in
this linking device.
AWL
Analog inputs.
AWL
Digital inputs.
AWL
Analog outputs.
AWL
Digital outputs.
N/A
RO
This alert is generated by any change to the static data.
N/A
RO
The block alarm is used for all configuration, hardware,
connection failure or system anomalies in the block.
The cause of the alert is entered in the subcode field.
The first alert to become active will set the Active
status in the Status attribute. As soon as the
Unreported status is cleared by the alert reporting task,
another block alert may be reported without clearing
the Active status, if the subcode has changed.
.