Parametrizing Via The "Easy Set-Up" Menu Function - ABB HART FEP300 Commissioning Instruction

Electromagnetic flowmeter
Table of Contents

Advertisement

4.3.2

Parametrizing via the "Easy Set-up" menu function

The device can be factory parametrized to customer specifications upon request.
If no customer information is available, the device is delivered with factory settings.
The setting of the most current parameters is summarized in the "Easy Set-up" menu. This
menu provides the quickest way to configure the device.
The Easy Set-up menu allows you to select the language, engineering unit for flowrate, flow
range, totalizer unit, pulse/frequency mode, pulse per unit, pulse width, damping, status of
current output during alarm (Iout at Alarm, Iout Low Alarm, Iout High Alarm).
The following section describes parametrization via the "Easy Set-up" menu function.
CI/FEP300/FEH300-EN
ProcessMaster / HygienicMaster
Press the ► key to change to the setup level of
the process display.
Use the ▲ + ▼ keys to select the "Standard"
menu item.
In the password menu, select "ok" (► key).
There is no factory default password.
Select "ok" (► key) to switch to the configuration
level without entering a password.
In the configuration level, use the ▲ + ▼ keys to
scroll to the "Easy Set-up" menu item and select
it by pressing the ► key.
Press the ► key and select the language. After
entering the settings, press the ◄ key to move to
the next menu item.
Press the ► key and select the mass flow unit.
After entering the settings, press the ◄ key to
move to the next menu item.