Startup Operation
32 - EN
ProcessMaster / HygienicMaster
Press the ► key and set the flow range end
value Qmax. After entering the settings, press the
◄ key to move to the next menu item.
Press the ► key and set the totalizer unit. After
entering the settings, press the ◄ key to move to
the next menu item.
Press the ► key and set the operating mode for
the pulse output. There are two operating modes
available:
•
"Pulse mode": In pulse mode, pulses per unit
are output. The relevant settings are provided
in the next menu.
•
"Frequency mode": In the frequency mode, a
frequency proportional to the flowrate is
output. The maximum frequency
corresponding to the mass flow range is
configurable.
The factory default is "pulse mode".
Press the ► key and set the pulses per unit for
the pulse output. After entering the settings,
press the ◄ key to move to the next menu item.
Press the ► key and set the pulses width for the
pulse output. After entering the settings, press
the ◄ key to move to the next menu item.
Press the ► key and set the damping. After
entering the settings, press the ◄ key to move to
the next menu item.
CI/FEP300/FEH300-EN