BATTERY FUSE
(e.g. ADEMCO No. 90-12)
GEL LEAD ACID TYPE.
FOR REPLACEMENT
BATTERY NORMALLY NEED NOT BE
USE SAME VALUE
REPLACED FOR AT LEAST 3 YRS.
BATTERY CAPACITY FOR EMERGENCY
STANDBY USE AT LEAST 4 HOURS.
3A
BLACK
BATTERY
CHARGING
12V, 4AH
VOLTAGE
+
RED
(e.g. ADEMCO
13.8VDC
No. 467)
OR 12V, 1.2AH
+
BATTERY
CONNECTOR TABS
TO DETERMINE TOTAL STANDBY LOAD
ON BATTERY, ADD 100mA TO TOTAL OF
AUX. POWER OUTPUT AND REMOTE
KEYPAD CURRENTS.
USE UL LISTED LIMITED
1
2
3
ENERGY CABLE FOR
ALL CONNECTIONS
AUX. POWER
FOR COMPLETE
10.5-13.8VDC
INFORMATION,
500mA MAX.
SEE INSTRUCTIONS
INTERRUPTS
ALARM RESET
TO 110VAC
UNSWITCHED
OUTLET (24-HR)
PLUG-IN
TRANSFORMER
16.5VAC, 25VA
(e.g. ADEMCO
No. 1321/TF2.
USE No. 1321CN
IN CANADA)
+
ALARM OUTPUT
10.5-13.8VDC, 2A MAX.
(600mA MAX. FOR UL USAGE,
INCLUDING AUX. POWER)
STEADY FOR BURGLARY/PANIC,
TEMPORAL SOUNDING FOR FIRE (e.g.
USE ADEMCO No. 740 SOUNDER,
Nos. 702 OR 719 SIREN, OR 12V BELL)
CONNECTION OF THE FIRE ALARM SIGNAL TO A FIRE
ALARM HEADQUARTERS OR A CENTRAL STATION
SHALL BE PERMITTED ONLY WITH THE PERMISSION OF
THE LOCAL AUTHORITY HAVING JURISDICTION. THE
BURGLAR ALARM SIGNAL SHALL NOT BE CONNECTED
TO A POLICE EMERGENCY NUMBER.
THESE OPTIONAL ITEMS
MAY ALSO BE USED
SEE THEIR INSTRUCTIONS
ADEMCO No. 5800TM
TRANSMITTER MODULE
(20mA)
(for No. 5827BD
Wireless Bidirectional Keypad)
AND/OR
ADEMCO No. 4285
VOICE MODULE (160mA)
AND/OR
ADEMCO No. 7720PLUS
or 7820 LONG RANGE RADIO
BLK
RED
GRN
YEL
4
5
6
7
8
9
10
+
OUTPUT
FOR FIRE
NOTE:
KEYPAD
CURRENT
MUST BE
INCLUDED
IN AUX.
CURRENT
DRAIN
CALCULA-
1000
1000
TIONS
OHMS
OHMS
EOLR
EOLR
REMOTE
KEYPAD(S)
• MAXIMUM LOOP RESISTANCE (EACH ZONE): 300 OHMS (PLUS EOLR)
• RESPONSE, ZONES 1–6: 300–500MSEC
REMOTE KEYPADS
• ZONE 3 CAN BE PROGRAMMED FOR N.C. SENSOR FAST RESPONSE
SYSTEM MUST BE
TO AN OPEN: 10MSEC MAX
PROGRAMMED WITH A
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
No. 5137AD OR 6139, BUT NEED
OPERATION IS SUBJECT TO THE FOLLOWING TWO
NOT REMAIN IN SYSTEM.
CONDITIONS: (1) IT MAY NOT CAUSE HARMFUL
AFTER PROGRAMMING, THE
INTERFERENCE, (2) IT MUST ACCEPT ANY INTERFERENCE
SYSTEM CAN USE:
THAT MAY CAUSE UNDESIRED OPERATION.
No. 4127(20mA), 4137AD (60mA),
5137AD (90mA), 6127 (20mA),
COMPLIES WITH FCC RULES, PART 68
6128 (30mA), 6137 (85mA),
FCC REGISTRATION NO. AC398U-68192-AL-E
6138 (100mA), OR 6139 (100mA).
RINGER EQUIVALENCE: 0.7B.
MULTIPLE KEYPADS MAY BE
USED, BUT USE MAX. OF 220 FT.
WARNING:
OF #22 WIRE OR 550 FT. OF #18.
ADT VISTA-10SE SUMMARY OF CONNECTIONS
firealarmresources.com
OPTIONAL
FOR UP TO 16 RF EXPANSION ZONES
ADEMCO 4281 or 5881* Type
RF RECEIVER
WIRELESS ZONES
AUX PWR
4281L:
UP TO 4
OUTPUT
4281M/4281H:
UP TO 8
TERMS
5881L:
UP TO 8
5881M/5881H/5881EH: UP TO 16
* 5882 Type IN CANADA
SET UNIT'S DIP SWITCH
OR COMBUSTION
FOR DEVICE ADDRESS OF "0"
(See receiver's instructions)
OPTIONAL
TO HI SIDE OF SELECTED ZONE
ADEMCO No. 4204
RELAY MODULE (180mA MAX)
ZONES 2–7
(4 OUTPUT RELAYS)
TO LO SIDE OF SELECTED ZONE
SET UNIT'S DIP SWITCH
ZONE 5
FOR DEVICE ADDRESS OF "1"
(IF PROGRAMMED FOR FIRE)
(See unit's instructions)
11
12
13
14
15
16
1000
1000
1000
1000
OHMS
OHMS
OHMS
OHMS
EOLR
EOLR
EOLR
EOLR
OWNER'S INSTRUCTION NOTICE NOT TO BE REMOVED. WEEKLY TESTING IS
REQUIRED TO ENSURE PROPER OPERATION OF THIS SYSTEM.
+
5
+
RED
BLK
-
4
EOL
POWER
+
SUPER-
-
VIOLET
VISION
4-WIRE SMOKE
RELAY
MODULE
DETECTOR
1000
2000
A77-716B
OHMS
OHMS
EOLR
LOCATED
EOLR
AT LOWER
+
+
RIGHT
HEAT
*
DETECTOR
OF CIRCUIT
-
BOARD
17
18
19
20
21
EARTH
GROUND
TIP
RING
TIP
RING
SEE
(BROWN)
(GRAY)
(GREEN)
(RED)
INSTRUCTIONS
FOR PROPER
GROUNDING
HANDSET
INCOMING
PHONE
LINE
TELEPHONE WIRING
(VIA RJ31X* JACK DIRECT
CONNECT CORD)
*IN CANADA, CA38A JACK
DOC LOAD No.: 3
WARNING:
TO PREVENT RISK OF
SHOCK, DISCONNECT TELEPHONE LINE
AT TELCO JACK BEFORE SERVICING
THIS UNIT.
THIS EQUIPMENT SHOULD BE INSTALLED IN
ACCORDANCE WITH THE NATIONAL FIRE
PROTECTION ASSOCIATION'S STANDARD 74
(NATIONAL FIRE PROTECTION ASSOC.,
BATTERYMARCH PARK, QUINCY, MA 02269).
PRINTED INFORMATION DESCRIBING PROPER
INSTALLATION, OPERATION, TESTING,
MAINTENANCE, EVACUATION PLANNING AND
REPAIR SERVICE IS TO BE PROVIDED WITH
THIS EQUIPMENT.