ADEMCO VISTA-10SE Installation Instructions Manual page 68

Hide thumbs Also See for VISTA-10SE:
Table of Contents

Advertisement

TO PROGRAM SYSTEM
STATUS AND
RESTORE REPORT
( 60 – 68, 70 – 75)
www.PDF-Zoo.com
Example 1. Pager displays:
This indicates that Subscriber No. 1234's system is reporting an Alarm (911),
due to zone 4 being faulted (004).
Example 2. Pager displays:
This indicates that Subscriber No. 1234's system is reporting an opening (001)
by User 5 (005).
Note that no restore reports are sent to the pager.
Important : Do not use AAV when Paging or Alarm Reports are being sent to
a Secondary number. If this is done, the call to the Secondary number by the
communicator after the alarm report will prevent the AAV from taking control
of the phone line, and the AAV "Listen in" session cannot take place.
Press 48
15-SECOND DIALER DELAY, BURGLARY
Press 49
PERIODIC TEST REPORT
Select the desired test report interval.
0 = none; 1 = 24 hours; 2 = weekly; 3 = 30 days. Default is 0
(none). Test Report Code entered in field
Reports with Subscriber No.
Press 50
SESCOA/RADIONICS SELECT
0 = Radionics (0–9, B–F reporting)
1 = SESCOA (0–9 only reporting)
Select 0 for all other formats. Default is 0.
With a 3+1 or 4+1 Standard Format: Enter a code in the first digit box:
1–9, 0, B, C, D, E, or F. Enter "# + 10" for 0, "# + 11" for B, "# + 12" for C,
"# + 13" for D, "# + 14" for E, "# + 15" for F.
CODES
A "0" ( not "# + 10") in the first digit box will disable a report.
A "0" ( not "# + 10") in the second digit box (if any) will result in automatic
advance to the next field when programming.
With an Expanded or 4+2 Format: Enter codes in both boxes (1st and 2nd
digits) for 1–9, 0, or B–F, as described above.
A "0" ( not "# + 10") in the second box will eliminate the expanded message
for that report.
A "0" ( not "# + 10") in both boxes will disable the report.
With Ademco Contact ID Reporting: Enter any digit (other than "0") in the
first box, to enable zone to report This is an "enabling" code only and is
disregarded in the actual reporting to the central office. Entries in the second
boxes will be ignored.
A "0" ( not "# + 10") in the first box will disable the report.
Examples:
For Code 3 (Single Digit), enter:
For Code 32 (Two Digits), enter:
For Code B2 (Hexadecimal) enter:
Press 60 TROUBLE REPORT CODE
This will be sent if a zone goes into trouble.
Press 61 BYPASS REPORT CODE
This will be sent when a zone is manually bypassed.
Press 62 AC LOSS REPORT CODE
Reports with Subscriber No. Timing of this report is random with
up to a 48-minute delay. The Restore report has a random delay
of up to about 12 minutes. If AC restores before the report goes
out, there is no AC restore report.
firealarmresources.com
1 2 3 4 – 9 1 1 – 0 0 4  
1 2 3 4 – 0 0 1 – 0 0 5
Enter 0 for no, or 1 for yes. Default is 0 (no delay).
3
3
# + 11
– 68 –
64 is sent.
0
2
2