1MRK 500 124-UEN
3.5.7.4
3.5.8
Operation Manual
Distributed busbar protection REB500
Disturbance recorder file (Detailed view / Upload )
The disturbance records are available in a zipped Comtrade file. The involved
disturbance recorder files has the naming convention
DRyyyyMMddhhmmssfff_aaa_nnnnn.ZIP
Table 7
Disturbance file names
Item
Description
yyyy
Year of the recording (Trigger time)
MM
Month of the recording (Trigger time)
dd
Day of the recording (Trigger time)
hh
Hour of the recording (Trigger time)
mm
Minute of the recording (Trigger time)
ss
Second of the recording (Trigger time)
fff
Miliseconds of the recording (Trigger time)
aaa
Station number (1-999)
nnnnn
Fault number (0-65535)
The name of the file can be changed if the records are transferred manually.

Event list

Protection system events are shown in chronological order. By correspondingly
setting the event filter, just protection events, system events or test events can be
viewed separately. Events with an invalid time tag can be excluded from the
display. You can choose between "User-defined" and "System-defined" event
texts.