Section 3
HMI500
3.6.6.2
3.6.6.3
3.6.6.4
56
Figure 44
New signal (list of available signals)
Delete signal
The assignment of a signal is cancelled by marking it in the dialog and clicking on
"Delete signal".
Caption
The name in the "Caption" column proposed by the program can be edited by
selecting it with the mouse. A caption can have a maximum of 20 characters.
Mode
The user can determine the response of the LED by clicking in the "Mode"
column. The following modes are possible:
Status: The current status of the signal is displayed.
Latching: The status of a LED is stored until one of the following occurs
§
A bay protection function picks up
§
A station protection function trips
§
It is reset via the local HMI
§
It is reset by HMI500
§
It is reset by a binary signal
The "Status LED on LMI" dialogue is saved by clicking "Ok". The dialogue "LED
statuses on the local HMI" is active again and a print of the LED labels can be
started by clicking "Print Labels" now. Before initiating a print job the "Print
Range" as well as the "Label Orientation" shall be adjusted.
1MRK 500 124-UEN
Operation Manual
Distributed busbar protection REB500