Operation Manual
Distributed busbar protection REB500

Trips

The trips generated by REB500 can be viewed in the trip list together with the
protection functions that caused them (Menu "Trips" / first column of list). In
addition the corresponding date/time information, source and values (if existing)
can be displayed.
The following trips can appear on the local HMI
TRIP(ITT):
BBP Trip:
BFP TRIP T1:
BFP TRIP T2:
OCDT TRIP:
PDF TRIP:
EFP TRIP:
EXTERNAL TRIP
DIST TRIP:
Further trip signal of Bay Protection (if existing)
All these information can be seen in the trip list by navigation via the right and left
arrow keys on the LHMI.
Date
Source
Date
Source
09:05:46
Bayname 1
09:05:46
Bayname 1
09:05:46
Bayname 1
09:05:46
Bayname 1
Date
Source
09:05:46
Zone BB01
09:05:46
Bayname 1
09:05:46
Bayname 1
Trip: corresponding bus zones
Phase related diff. and restr. currents
Current of each phase
Current of each phase
Current
Current
Current
Zone (Zone 1,2,3,4, or Zone 5 for the 'final zone'),
impedance and fault location
*1)
L1 3604A
L2 0A
3604A
-
-
-
-
-
Id = 3604A Ih = 3604A
3604A
-
Section 4
Local HMI
*3) *5)
Value
Value
L3 0A
L0 3604A
-
-
-
-
-
-
Value
-
-
81