ABB REB500 Operation Manual page 97

Hide thumbs Also See for REB500:
Table of Contents

Advertisement

1MRK 500 124-UEN
Alarm
Repetitive Diff Current Alarm
Repetitive Invalid BU Currents
Repetitive Output Relays
blocked
Repetitive BU restarts
Repetitive CU restarts
CIM HW Failure
CPC HW Failure
BU HW Failure
Missing PSM HW Module
Missing Red. PSM HW Module
Missing BIO HW Module
Missing TRM HW Module
Missing PIO HW Module
Wrong TRM HW Module
Wrong PSM HW Module
Wrong Red. PSM HW Module
BIO channels mismatch
IP address conflict
1) only once during start-up or normal running state
2) only once during start-up
Table 24
Permanently blocked state
Alarm
Permanently Blocked
Operation Manual
Distributed busbar protection REB500
Event
Detection setting
Major_Error 018
60 per 3'600 sec
Major_Error 019
30 per 60 sec
Major_Error 020
30 per 600 sec
Major_Error 021
3 per 600 sec
Major_Error 022
3 per 600 sec
Major_Error 023
once 1)
Major_Error 024
once 1)
Major_Error 025
once 1)
Major_Error 026
once 2)
Major_Error 027
once 2)
Major_Error 028
once 2)
Major_Error 029
once 2)
Major_Error 030
once 2)
Major_Error 031
once 2)
Major_Error 032
once 2)
Major_Error 033
once 2)
Major_Error 034
once 2)
Major_Error 075
once 2)
Event
Detection setting
Major_Error 176
-
Description
If a Repetitive Diff Current Alarm is activated, the target
blocks permanently
If a Repetitive Invalid BU Currents alarm is activated, the
target blocks permanently
If a Repetitive Output Relays blocked alarm is activated, the
target blocks permanently
In case of Repetitive BU restarts , the target blocks
permanently
In case of Repetitive CU restarts , the target blocks
permanently
If the diagnosis detects any HW related failure , the CIM
blocks permanently
If the diagnosis detects any HW related failure , the CPC
blocks permanently
If the diagnosis detects any HW related failure , the BU
blocks permanently
If the required PSM HW module is missing, the target blocks
permanently
If the configured/required redundant PSM HW module is
missing, the target blocks permanently
If the configured/required BIO HW module is missing, the
target blocks permanently
If the required TRM HW module is missing, the target blocks
permanently
If the configured/required PIO HW module is missing, the
target blocks permanently
If the configured and physical assembled TRM HW module
do not match, the target blocks permanently
If the configured and physical assembled PSM HW module
do not match, the target blocks permanently
If the configured and physical assembled redundant PSM
HW module do not match, the target blocks permanently
If binary input or output channels configured on physical
channels that are not available, the target blocks
permanently
If an IP address configuration problem occurs (The main
reason is that two interfaces are configured with the same IP
address), the target blocks permanently
Description
If the error handling detects start-up or repetitive error
causes (see Table 15), the permanently blocked state is set
Section 6
Troubleshooting
89