ABB REB500 Operation Manual page 88

Hide thumbs Also See for REB500:
Table of Contents

Advertisement

Section 4
Local HMI
80
The following alarms can be displayed:
Busbar protection blocked
Breaker failure protection blocked
End fault protection blocked
OCDT blocked Overcurrent protection blocked
Pole discrepancy protection blocked
Bay unit alarm
Contacts blocked
Inspection/Maintenance
Inspection alarm
Auxiliary voltage failed
Trip transferred
Circuit breaker alarm
Isolator alarm
Test generator active
Contacts blocked
HW configuration mismatch
Pow.sup. fault
Power supply 2 failed
AC Fail
Major error
BU problem
CU problem
General alarm
Viewing the event list and disturbance records is recommended
should an alarm occur. The corresponding procedure is described in
3.5.7.
"Disturbance recorder" respectively
Avoid performing switching operations in the event of the
following alarms before the failure has been analyzed by
correspondingly trained personnel:
Isolator alarm
Switch inhibit
Differential current alarm
Inspection and maintenance
Non-observance of this precaution can cause mal-operation in
normal operation or a failure to trip in response to a fault.
Isolator alarm may only be acknowledged by appropriately
trained and authorized personnel. Non-observance of this precaution
can cause mal-operation in normal operation or a failure to trip in
response to a fault.
1MRK 500 124-UEN
3.5.8.
"Event list".
Operation Manual
Distributed busbar protection REB500

Advertisement

Table of Contents
loading

Table of Contents