Wiring
6.1.1
Mechanical connection of the base modules
Procedure:
Use a flat blade screwdriver (DIN 5264-A)!
}
Strip the wire back 8 mm.
}
If necessary, label the connection level with a colour marker [3].
}
Base module with screw terminals:
}
–
–
–
–
Base module with cage clamp terminals:
}
–
–
–
–
Operating Manual PSSu E S 2DOR 10(-T)
22047-EN-05
Use a screwdriver to loosen the screw on the screw terminal [1]
Insert the stripped cable into the round fixing hole [2], as far as it will go.
Tighten up the screw on the screw terminal.
Check that the cable is firmly seated.
Insert the screwdriver [4] into the square hole [1].
Insert the stripped cable into the round fixing hole [2], as far as it will go [5].
Pull out the screwdriver [6].
Check that the cable is firmly seated.