Wiring
Please note:
The minimum cable cross section for field connection terminals on the base modules is
}
0.14 mm
The maximum cable cross section for field connection terminals is:
}
On base modules with screw terminals:
}
Use copper wiring.
}
Operating Manual PSSu E S 2DOR 10(-T)
22047-EN-05
(AWG26).
2
Digital inputs: 1.5 mm
2
Digital outputs: 2.0 mm
Inputs/outputs on the counter modules: 1.5 mm
Analogue inputs/outputs: 1.5 mm
Communication cables: 1.5 mm
Test pulse outputs: 1.5 mm
Power supply: 2.5 mm
2
Functional earth: 2.5 mm
If you use a multi-strand cable to connect the I/Os, it is recommended that you use
ferrules conforming to Parts 1 and 2 of DIN 46228, 0.14 ... 1.5 mm
although this is not essential. To crimp the ferrules you can use crimp pliers (crimp
form A or C) conforming to EN 60947-1, such as the PZ 1.5 or PZ 6.5 from
Weidmüller, for example.
Maximum torque setting: 0.8 Nm
(AWG16)
(AWG14)
2
(AWG16)
2
(AWG16)
2
(AWG16)
2
(AWG12)
(AWG12)
2
[4]
[5]
[6]
(AWG16)
2
, Form A or C,
2