2-9-4. Setting with Configuration Tool

Some settings of functions configurable with the Configuration Tool may increase risks.
Make sure the Responsible Person conduct a thorough risk assessment analysis before
managing and changing the settings. Unintended changes to the settings may cause a
person to go undetected, resulting in serious injury.
The user can make changes to the settings by the Configuration Tool.
Interlock function
Function
Start Interlock
Restart Interlock
* Setting parameters of this function can be saved according to the states where the Muting function is
enabled and disabled, respectively. After changing the Muting function from Enable to Disable or
from Disable to Enable, also check the settings of this function again.
Refer to
Considerations for enabling and disabling Muting function under 2-1. Combination of Functions
for more information.
Pre-Reset function
Function
Pre-Reset
Maximum number of times F3SG-R can be blocked *3 infinite
Maximum permissible time from input of PRE-RESET
signal to input of RESET signal
*1. When the Pre-Reset is enabled, it precedes all other interlock functions and the parameters of Start
Interlock and Restart Interlock are ignored.
*2. It is not possible to configure the Pre-Reset function together with the Muting function. To enable
settings of the Pre-Reset function, disable the Muting function.
In addition, setting parameters of the following functions can be saved according to the states
where the Muting function is enabled and disabled, respectively. After changing the Muting function
from Enable to Disable or from Disable to Enable, also check the settings of these functions again.
Affected functions: External Device Monitoring (EDM), Start Interlock, Restart Interlock, Auxiliary
Output, Lamp Output
*3. The minimum number of times is fixed to 1.
Make sure the Position 8 of the DIP Switch is set to Configuration Tool Enabled to activate the settings by the
Configuration Tool.
Refer to Safety Light Curtain Configuration Tool for Model F3SG (SD Manager 2) User's Manual for more
information on setting this function by the Configuration Tool.
Factory Default Setting
Muting function enabled*
Muting function disabled*
Disable
Disable
Disable
Disable
Factory Default Setting
Disable
8 s
System Operation and Functions
Available Parameters
Enable/Disable
Enable/Disable
Available Parameters
Enable*1*2/Disable
1 to 9 times in 1-time increments, or infinate
1 to 60 s in 1-s increments
E
F3SG-R
39
User's Manual